Products
首页 > 产品中心 > Switchgear & Transformer
RMNS series Low Voltage Switchgear
产品说明

++++General:
     Electric Powertek Company strives to bring our customers the latest technology and competitive power system and best service for transmission and distribution line. The RMNS system are suitable for applications in all fields concerning the generation, distribution and use of electrical energy, e. g., they can be used as: Main and sub-distribution boards for energy and Motor current supply of Motor Control Centers
    • Utility companies
    • Power plants
    • Oil refineries
    • Off-shore drilling platforms
    • Production facilities
    • Buildings for other than dwelling purposes.
    The RMNS system is full complied with GB7251.1, IEC 439-1, EN 60 439-1, VDE 0660 part 500, BS 5486 Part 1 and UTE 63-410.
++++ Service environment:
    a) Air temperature: Maximum temperature: +40℃; Minimum temperature:-5℃; +35℃ average over 24 hours.
    b) Humidity: Monthly average humidity 50% in clear air with the maximum +40℃; Higher relative humidity is permitted in lower temperature. For example, the      

        relative humidity is 90% for the temperature of +20℃. Variety of temperature should be taken into consideration of moisture.
    c) Altitude above sea level: Maximum installation altitude: 2000m or more higher;
Note: Adaption to other ambient temperatures is possible under consideration of the reduction factors. It must be ensured that indoor conditions are maintained for the place of installation. Moisture condensation on the switchgear components must be prevented by suitable measures such as heating and/or ventilation. Installation up to 1000 m above sea level for higher locationss the reduction factors has to be taken into consideration.
++++Extreme conditions:
    A suitable surface treatment is applied to ensure tropicalization. With the aid of accessories and strengthened parts the RMNS system meets the safety requirements for earthquake-prone areas.
   · in tropical areas
   · in earthquake-prone areas
   · in shelters
   · in shipbuilding
   · in offshore switchboards

++++Main technical data:


 No.

  Item

 Unit

  data

 1

 Rated voltage

  V

 Up to 690

  2

 Rated current for system

 A

  4000(special to 6300A)

 3

                                        Horizontal  Busbar

 Rated current for busbar
                                        Vertical Busbar

  A

 Busbar 6300 *extremely*

1600 @+40℃

 4

  Rated frequency

 HZ

 2000*Note*

 5

Power frequency with voltage 1min

 kV

 8

 6

                                      Horizontal Busbar

Rated Short-timeWithstand Current

                                      Vertical Busbar

 kA/1S

   55-100/105-250

 60/130-150

 7

Over voltage class

III

 8

 Pollution Degree

 3

 9

 Protection Degree

  IP30/IP40/IP54

 10

 Outline Dimensions(H*W*D)

 mm

   2200×600(800/1000)×600(800/1000)


Note:
1. The current of vertical busbar is extremely up to 2000A@+35℃,(+40℃ with cooler) .
2. Protection Degree of IP54 is taken into consideration for special design if needed.